Technical features – CIRCUTOR CDP-0 User Manual

Page 67

Advertising
background image

CDP

Instruction Manual

67

7.- TECHNICAL FEATURES

AC power supply

Rated voltage

110…264

V ̴

Frequency

50 … 60 Hz

Consumption

6 VA …10 VA

Installation category

CAT III 300 V

DC Power supply

Rated voltage

12 V

Consumption

4 W

Installation category

CAT III 300 V

Voltage measurement circuit

Voltage measurement margin

10…300 V

̴

Frequency measurement margin

50 … 60 Hz

Input impedance

400 kΩ

Minimum measurement voltage (Vstart)

10 V

Installation category

CAT III 300 V

Current measurement circuit

Nominal current (In)

… / 250 mA

Overcurrent

105% In

Maximum current, impulse < 1s

According to the current sensor

Minimum measurement current (Istart)

10 mA

Installation category

CAT III 300 V

Measurement accuracy

Voltage measurement

0.5%

Current measurement

0.5%

Power measurement

0.5%

Energy measurement

1%

Relay outputs

Quantity

4

Maximum voltage, open contacts

250 V

̴

Maximum current

6 A

̴

Maximum switching power

1500 W

̴

Electrical life

60x10

3

cycles

Mechanical working life

10x10

6

cycles

Digital inputs

Quantity

4

Type

Potential-free contact

Insulation

Optoisolated

Communications

User interface

Ethernet

Communications with the inverter

Field bus

RS-232/RS-485/RS-422

Baud rate

Depending on the inverter

(See application notes)

Stop bits

1

Parity

no parity

Communications with other units

Field bus

RS-485

Communications protocol

Modbus

Baud rate

4800-9600-19200-38400

Stop bits

1

Parity

no parity