Quick startup – Flowserve Limitorque Master Station III User Manual

Page 12

Advertising
background image

Limitorque Master Station III FCD LMENIM5001-02 – 12/13

12

3

Quick Startup

3.1 Master Station Quick Startup Instructions

1. Connect earth ground (#14AWG minimum) wiring, MOV network cables (Belden

#3074F/#9841/#3107), and power cable.

2. Apply power to the Master Station.

3. Wait for the Master Station to display the start-up screen.

4. Touch the screen, then enter user name “FLOW”. Select Enter.

5. Enter password “100” when prompted. Select Enter.

6. Next select “System Configuration” then “Redundant Configuration”.

7. Set the requested mode to “Disabled”, startup mode to “Active”, and redundancy mode

to desired setting.

8. Next select the “back” button and in the “System Configuration” select “User Administration”.

9. Set up user accounts per Section 8.2.4.

10. Select “MOV Network Config” and set up per Section 8.2.6.

11. Select “DCS Configuration” and set up per Section 8.2.5.

For remote DCS control, the three primary registers of interest are:

- 46001: Register for HS Status (Read Only): 0=idle, 1=standby, 2=hot
- 46002: Register for Host System to toggle (Write Only): 3=toggle state
- 46191: Register for Internal Program Execution Heartbeat/Watchdog (Read Only):

Updates every scan, 8-bit integer

Further adjustments may be made by following the procedures outlined in this manual.

12. Tap the “Back” button to return to the “System Configuration” screen.

13. Select “Redundant Config” and change the requested mode to “Active”.

Advertising