4 error messages, 5 network communication, 2 dcs communication via modbus tcp/ip – Flowserve Limitorque Master Station III User Manual

Page 66: 3 msiii communication to the mov network

Advertising
background image

Limitorque Master Station III FCD LMENIM5001-02 – 12/13

66

flowserve.com

10.4 Error Messages

Problem Saving File – Media Error (Full, Write Protected, Corrupted)

No USB Device Selected - Configuration save attempted without a USB device inserted in a USB port,
and selected.

Error Adding User - Duplicate User entry

Error Saving To Config File - Media Error (Full, Write Protected, Corrupted)

10.5 Network Communication

10.5.1 DCS communication via RS-232/422/485

Unable to establish comm’s with the DCS

a. Confirm null modem cable connection, if using RS-232

b. Verify DCS address setting

c. Verify baud rate, handshaking, start bit settings

d. Check host system settings

e. Test the cable, replace if defective

10.5.2 DCS communication via Modbus TCP/IP

Unable to establish comm’s with the DCS

a. Confirm IP address settings

b. In command mode, ping the MSIII, if no response, verify the MSIII and the host are on

the same network

c. Verify Ethernet path from host to the MSIII

10.5.3 MSIII communication to the MOV network

Unable to establish comm’s with the MOV’s

a. Confirm proper cable connections on the first MOV in the loop and the MSIII. RS-485

is polarity sensitive

b. Confirm RS-485 baud rate settings match MOV baud rate settings

c. Confirm MSIII is configured for Modbus RTU mode

d. Verify timing settings (timeout, prop delay, RTS on delay)

Advertising