Limitorque Master Station III FCD LMENIM5001-02 – 12/13

flowserve.com

Figure 8.25 - FC-03 Sample Data Table

NOTE: Data table shown with only registers 8 and 9 (Position and Status) selected.

This function code is used to read the binary contents of holding registers. This function code is
typically used during the network polling cycle. A network poll must consist of field unit registers 8
(Position) and 9 (Status) at a minimum. See Table 8.4 for a complete listing of the holding registers.

Example of read multiple registers command
Poll Master Station for 2 registers starting at register 27 (i.e., field unit #14)
Query: 0103001A0002E5CC
Response: 010304003200445BCF

Table 8.3 - Function Code -03 Example Message Breakdown

Query

Response

01

MSIII Unit Address

01

MSIII Unit Address

03

Function

03

Function

00

Starting Address Hi

04

Byte Count

1A

Starting Address Lo

00

Data Hi (Register 40027; MOV14)

00

No. of Points Hi

32

1

Data Lo (Register 40027; MOV14)

02

No. of Points Lo

00

Data Hi (Register 40028; MOV14)

E5CC

Error Check (CRC)

44

2

Data Lo (Register 40028; MOV14)

5BCF

Error Check (CRC)

NOTE 1: 0032h equals 50 decimal (actuator position in percent format)

NOTE 2: 0044h equals 68 decimal or 0000 0000 0100 0100 (actuator stopped between limits in local
mode)