56

8.2.6 MOV Network Config

The MOV Network Config screen (Figure 8.32) provides access to communication parameters
essential for connecting the Master Station to all assigned field units. By selecting the Next button,
the screen will advance to Active MOVs display (Figure 8.33) which allows the user to add additional
field units to the network. After finishing the MOV activations desired, simply select the Poll Priority
tab to advance to the Polling Priority view (Figure 8.34). This screen enables the user to set the poll
cycle interval for each activated MOV. After the MOV network has been configured, please save the
settings under the System Configuration screen (Figure 8.2).

NOTE: MOV Network Config is disabled when the unit is running in “Active” mode. To turn off
“Active” mode and make changes to the MOV Network configuration, go to the System Configuration
menu as detailed in Section 8.1 and select the “Redundant Config” button. Under the Requested
Mode title, select the “Disabled” button and tap the “Back” button to return to the System
Configuration screen. All the MOV Network configuration changes can now be accessed by tapping
the “MOV Network Config” button and following the proceeding directions.

Figure 8.32 - MOV Network Configuration

NOTE: The timeout and prop delay settings may need to be adjusted based on the actuator series,
size of the network, baud rate, and cable type/length.

Figure 8.33 - Active MOVs