Limitorque Master Station III FCD LMENIM5001-02 – 12/13

54

Table 8.11 - Function Code -16 Message Breakdown

Query

Response

01

MSIII Unit Address

01

MSIII Unit Address

10

Function

10

Function

13

Starting Address Hi

13

Starting Address Hi (Register 45050; MOV50)

B9

1

Starting Address Lo

B9

Starting Address Lo (Register 45050; MOV50)

00

Number of Registers Hi

00

Number of Registers Hi

03

Number of Registers Lo

03

Number of Registers Lo

06

Byte Count

5569

Error Check (CRC)

03

Preset Data Hi (MOV 50)

00

2

Preset Data Lo (MOV 50)

03

Preset Data Hi (MOV 51)

00

Preset Data Lo (MOV 51)

03

Preset Data Hi (MOV 52)

00

Preset Data Lo (MOV 52)

6ABB

Error Check (CRC)

NOTE 1: 13B9h equals register address 45050 (field unit 50 command register)

NOTE 2: 0300h requests the register to be preset with 768d (Field unit close)
See Tables 8.12 and 8.13 for valid register operations. For further reference, see DDC (Modbus) Field

Unit Installation and Maintenance manual LMENIM2329.

Table 8.12 - Valid Command Register Operations

Host Commands to Field Unit Register 1

Value (Decimal)

Function

Null Command

0

No action

Open

256

Open actuator

Stop

512

Stop actuator

Close

768

Close actuator

Reset Field Unit

1024

Reset processor

Start Network ESD

1280

ESD initiate

Stop Network ESD

1536

ESD terminate

Engage Relay #1

2304

S1 or R1 (opt)

Engage Relay #2

2560

S2 or R2 (opt)

Engage Relay #3

2816

R3 (opt)

Engage Relay #4

3072

R4 (opt)

Engage Relay #5

3328

R5 (opt)

Engage Relay #6

3584

R6 (opt)

Engage Relay #7

3840

R7 (opt)

Disengage Relay #1

4352

S1 or R1 (opt)

Disengage Relay #2

4608

S2 or R2 (opt)

Disengage Relay #3

4864

R3 (opt)

Disengage Relay #4

5120

R4 (opt)

Disengage Relay #5

5376

R5 (opt)

Disengage Relay #6

5632

R6 (opt)

Disengage Relay #7

5888

R7 (opt)

Move-To (Enable)

1

6656

Initiates “move-to”

Engage Relay #8

6912

R8 (opt)

Disengage Relay #8

7168

R8 (opt)

Note 1: This is a two-step command. A valid value must be written to Register 2 before issuing this command.