4 master station network topologies, Legend, Figure 4.6 - modbus redundant loop topology – Flowserve Limitorque Master Station III User Manual

Page 18

Advertising
background image

Limitorque Master Station III FCD LMENIM5001-02 – 12/13

18

18

4.4 Master Station Network Topologies

Notes:

1) Belden 3074F, 3105A, or 9841 shielded cable is recommended.
2) Correct polarity for field unit and network controller

connection is necessary for proper operation.

3) Connections shown are typical. The number of

MOVs shown may not indicate true system size.

4)

Earth ground: ground rod

5)

Earth ground: ground rod or lug in
actuator if actuator is grounded.

Channel A

Channel B

MASTER STATION III

A1*

MOV-1

See Note 5

A2*

N/C

MOV-249

See Note 5

N/C

MOV-3

See Note 5

N/C

4
5

14

3

3

3

3

3

3

13

A2

A1

A1*

A2*

4
5

14
13

A2

A1

A1*

A2*

4
5

14
13

A2

A1

N/C

N/C

MOV-2

See Note 5

A1*

A2*

4
5

14
13

A2

A1

MOV-248

See Note 5

A1*

A2*

4
5

14
13

A2

A1

MOV-250

See Note 5

A1*

A2*

4
5

14
13

A2

A1

Diagnostic Note:

Polarity and level of the network’s data connection

can be checked by measuring voltage between data

and data* terminals. This voltage should be greater

than +200 mV DC with network controller (host)

network ports disconnected. Data terminal is

positive with respect to data* terminal.

Earth Ground Note:

If low impedance earth ground is not available at each

actuator, contact engineering for alternative earth

ground surge protection strategies.

Legend

MOV

N/C
Data terminal is positive with respect to

data* terminal

13

14

5

4

- Motor-operated valve

- Data A1

- Data A1*

- Data A2

- Data A2*

- Shield

- No connection

Figure 4.6 - Modbus Redundant Loop Topology

Advertising