Flowserve Limitorque Master Station III User Manual

Page 48

Advertising
background image

Limitorque Master Station III FCD LMENIM5001-02 – 12/13

48

Table 8.4 - Register Definitions (continued)

Register #

Description

Meaning

13

Digital Inputs 2

Value of 16 Digital Inputs

Bit 0 Analog board 1 present

Bit 1 Analog board 2 present

Bit 2 Analog Input 1 lost

Bit 3 Analog Input 2 lost

Bit 4 Network Channels A/B timed out

Bit 5 Relay board R5-R8 present

Bit 6 DDC board present

Bit 7 Relay board R1-R4 and RM present

Bit 8 Foundation Fieldbus board present

Bit 9 Profibus PA board present

Bit 10 CSE chosen for input 2

Bit 11 DeviceNet board present

Bit 12 Phase lost

Bit 13 Phase reverse

Bit 14 Not Used

Bit 15 Profibus DP board present

14

Compartment Temp

Internal compartment temperature

1

15

Torque

Torque Value (0-100% unit rating)

16

Current State

Bits 0-15 Not Used

17

Field Unit Holding Register

Special Applications Only

18

Field Unit Holding Register

Special Applications Only

19

Field Unit Holding Register

Special Applications Only

20

Field Unit Holding Register

Special Applications Only

21

Field Unit Holding Register

Special Applications Only

22

Field Unit Holding Register

Special Applications Only

23

Field Unit Holding Register

Special Applications Only

24-44

Reserved

Special Applications Only

45-47

Not Named

Special Applications Only

48

TP_START_POSITION

Special Applications Only

49

TP_STOP_POSITION

Special Applications Only

50

TP_SAMPLE

Special Applications Only

51

TP_MID_T_HIGH

Special Torque Applications Only

52

TP_MID_T_POS

Special Applications Only

53

TP_MID_T_AV_VAL

Special Torque Applications Only

54

TP_STOP_VAL

Special Applications Only

55

TP_BEFORE_ MID_T_HIGH

Special Torque Applications Only

56

TP_AFTER_ MID_T_HIGH

Special Torque Applications Only

Note 1: Range is +90°C to -55°C. High byte 00 indicates positive (+) and 01 indicates negative (-). Low byte

indicates temperature value.

Advertising