2 modbus fc 03 read holding registers – Flowserve Limitorque Master Station III User Manual

Page 44

Advertising
background image

Limitorque Master Station III FCD LMENIM5001-02 – 12/13

44

Table 8.2 - Function Code -02 Example Message Breakdown

Query

Response

01

MSIII Unit Address

01

MSIII Unit Address

02

Function

02

Function

00

Starting Address Hi

02

Byte Count

50

Starting Address Lo

04

1

Data (Inputs 10088 - 10081; MOV2)

00

No. of Points Hi

08

2

Data (Inputs 10096 - 10089; MOV2)

10

No. of Points Lo

BABE

Error Check (CRC)

79D7

Error Check (CRC)

NOTE 1: 04h equals 0000 0100 (actuator stopped in mid-travel input bit is ON)
NOTE 2: 08h equals 0000 1000 (actuator Channel B fault input bit is ON)

8.2.5.3.2 Modbus FC 03 Read Holding Registers

Touching the “Modbus FC 03 Read Holding Registers” button will take the user to the Modbus Holding
Registers screen (Figure 8.24) for selection of desired field unit holding registers 3-15. Note that registers
8 and 9 are always included in the data table.

Figure 8.24 - Modbus Holding Registers

Selecting the “Next” button will advance the screen to the following sample data table screen: