Limitorque Master Station III FCD LMENIM5001-02 – 12/13

flowserve.com

Example of force multiple coils command
Force coil 2 of field unit 23 ON. This will CLOSE the valve controlled by field unit 23. Additionally, force

coil 1 of field unit 24 ON. This will OPEN the valve controlled by field unit 24.
Query: 010F002D000201033290
Response: 010F002D00024403

Table 8.7 - Function Code -15 Example Message Breakdown

Query

Response

01

MSIII Unit Address

01

MSIII Unit Address

0F

Function

0F

Function

00

Coil Address Hi

00

Coil Address Hi (Coil 46; MOV23)

2D

Coil Address Lo

2D

Coil Address Lo (Coil 46; MOV23)

00

Quantity of Coils Hi

00

Quantity of Coils Hi

02

Quantity of Coils Lo

02

Quantity of Coils Lo

01

Byte Count

4403

Error Check (CRC)

03

Force Data Lo

3290

Error Check (CRC)

NOTE 1: 002D00020103h equals coil addresses 00101101b (field unit 23, coil 2) and 00101110b (field unit 24, coil 1)

8.2.5.3.4 Modbus FC 06/16 Preset Registers

Touching the “Modbus FC 06/16 Preset Registers” button will take the user to the Modbus Holding Registers screen
(Figure 8.28) for configuration of desired number of holding registers to be written per MOV. The 06 command presets
a value into a single-holding register (Figure 8.28), while the 16 command presets a value into a block of multiple
holding registers (Figure 8.29). The data table for these function codes permit either one or two write registers per
field unit.

Figure 8.28 - Modbus Holding Registers-One Per MOV

Figure 8.29 - Modbus Holding Registers-Two Per MOV