Limitorque Master Station III FCD LMENIM5001-02 – 12/13

46

Table 8.4 - Register Definitions

Register #

Description

Meaning

1

Command

Registers 1 and 2 are write-only registers used for Modbus

Function Code 06

2

Argument

Registers 1 and 2 are write-only registers used for Modbus

Function Code 06

3

Analog Output 1

Position (APT) Value (Default 0-100)

1

4

Analog Output 2

Torque (ATT)

5

Value (Default 0-100)

1

5

Analog Input

Main Power (Volts)

6

Analog Input

Analog Input 1 (Default 0-100)

1

User 4-20 mA / 0-20 mA Input

7

Analog Input

Analog Input 2 (Default 0-100)

1

User 4-20 mA / 0-20 mA Input

8

Position

Valve Position, Scaled Value (Default 0-100)

1

9

Status Register

16 Bits of field unit status:

Bit 0 Opened

Bit 1 Closed

Bit 2 Stopped in Mid-Travel

Bit 3 Opening

Bit 4 Closing

Bit 5 Valve jammed

Bit 6 Not in Remote

2

Bit 7 Combined fault

3

Bit 8 Over temperature fault

Bit 9 Future Implementation

Bit 10 Network Channel A fault

4

(Terminals 13 and 14)

Bit 11 Network Channel B fault

4

(Terminals 5 and 4)

Bit 12 Open torque switch fault

Bit 13 Close torque switch fault

Bit 14 Valve-operated manually fault

Bit 15 Phase error

NOTE 1: Default value is scaled 0-100 of span. Changes made to “Analog Scale” affect analog registers (3, 4, 6, 7, 8)

and “move-to” commands. (0-100, 0-255, 0-4095)

NOTE 2: MX/DDC actuators shipped after 2nd QTR, 1999, have the following definition of Register 9 Bit 6. When this

bit has a value of 1 or true, the actuator is in LOCAL or STOP (unavailable for network control). The actuator
selector switch in REMOTE (available for network control) is indicated by Register 12 Bit 0 having a value of 1
or true.

IMPORTANT: Verify host program when installing an MX/DDC actuator shipped after 2nd QTR, 1999, on a network
commissioned before 2nd QTR, 1999, for proper indication of selector switch values. Failure to verify proper selector
switch indication at the host may cause unsafe conditions at the facility.

MX/DDC actuators shipped prior to 2nd QTR, 1999, have the following definition for Register 9 Bit 6. When this bit has
a value of 1 or true, the actuator selector switch is in LOCAL mode. This bit does not indicate STOP or REMOTE. The
actuator selector switch in REMOTE (available for network control) is indicated by Register 12 Bit 0 having a value of 1
or true. Register 9 Bit 6 value 0 (zero) or false AND Register 12 Bit 0 value 0 (zero) or false indicates selector switch is
in the STOP position.

NOTE 3: Combined Fault bit is high when Bit 5 or 8 or 9 or 15 or (Bits 10 and 11) is high.

NOTE 4: Channel A is physical connection A1. Channel B is physical connection A2.

NOTE 5: The ATT feature will calculate the percent of torque seen with respect to the configured unit torque setting.This

percent torque value will be reflected in modbus register 3, when configured for Analog Out 1, and modbus
register 4, when configured for Analog Out 2. Example: If the unit torque setting is 75%, the modbus register
will be populated with a percent torque value scaled from 0% to 75% of the unit-rated torque.