Flowserve Limitorque Master Station III User Manual

Page 53

Advertising
background image

53

Limitorque Master Station III FCD LMENIM5001-02 – 12/13

flowserve.com

50

1

Register Address Lo

50

Register Address Lo (Register 45201; MOV101)

05

Force Data Hi

05

Force Data Hi

00

2

Force Data Lo

00

Force Data Lo

8F7B

Error Check (CRC)

8F7B

Error Check (CRC)

NOTE 1: 1450h equals register address 45201 (field unit 101 command register)

NOTE 2: 0500h requests the register to be preset with 1280d (Start Network ESD)

Example of a two-command write to a single register
“Move-To” Command. Move an actuator at address 45 to 42% open by first writing the value of 42 to
register 45090. After receiving a response, write the value of 6656 to register 45089. The actuator will
then move to a position of 42% open. First Command:
Query: 010613E2002AACA7
Response: 010613E2002AACA7

Table 8.9 - Function Code -06 Second Command Message Breakdown

Query

Response

01

MSIII Unit Address

01

MSIII Unit Address

06

Function

06

Function

13

Register Address Hi

13

Register Address Hi (Register 45090; MOV45)

E2

1

Register Address Lo

E2

Register Address Lo (Register 45090; MOV45)

00

Force Data Hi

00

Force Data Hi

2A

2

Force Data Lo

2A

Force Data Lo

ACA7

Error Check (CRC)

ACA7

Error Check (CRC)

NOTE 1: 13E2h equals register address 45090 (field unit 45 argument register)

NOTE 2: 002Ah equals 42d

Second Command:
Query: 010613E11A00D618
Response: 010613E11A00D618

Table 8.10 - Function Code -06 Message Breakdown

Query

Response

01

MSIII Unit Address

01

MSIII Unit Address

06

Function

06

Function

13

Register Address Hi

13

Register Address Hi (Register 45089; MOV45)

E2

1

Register Address Lo

E2

Register Address Lo (Register 45089; MOV45)

1A

Force Data Hi

1A

Force Data Hi

00

2

Force Data Lo

00

Force Data Lo

D618

Error Check (CRC)

D618

Error Check (CRC)

NOTE 1: 13E1h equals register address 45089 (field unit 45 command register)

NOTE 2: 1A00h equals 6656d

Example of multiple register write command
Write the command to close an actuator to field units 50, 51, and 52. This corresponds to writing the
value 768 into command registers 45050, 45051, and 45052.
Query: 011013B90003060300030003006ABB
Response: 011003B900035569