Flowserve Limitorque Master Station III User Manual

Page 43

Advertising
background image

43

Limitorque Master Station III FCD LMENIM5001-02 – 12/13

flowserve.com

Table 8.1 - Status Bit Definitions (continued)

Bit Number

Modbus

Bit

Address

MX/DDC

183

182

Not used

184

183

Not used

185

184

User Input 0

186

185

User Input 1

187

186

User Input 2

188

187

Remote stop input

189

188

Remote open input

190

189

Remote close input

191

190

Not used

192

191

Not used

193

192

Analog board 1 present

194

193

Analog board 2 present

195

194

Analog Input #1 lost

196

195

Analog Input #2 lost

197

196

Network Channels A/B timed out

198

197

Relay board R5-R8 present

199

198

DDC board present

200

199

Relay board R1-R4 and RM present

201

200

FF board present

202

201

PB PA board present

203

202

CLE assigned for input 2

204

203

DNET board present

205

204

Lost Phase Input

206

205

Phase Reverse Input

207

206

Not used

208

207

PB DP board present

From DCS, user must address the Master Station III and poll according to the FC-02 data table. See
the following example of a request/response exchange between the DCS and the Master Station III
using the Standard mapping scheme.

Example of read inputs command
Poll Master Station for 16 inputs starting at input 81 (i.e., field unit #2)
Query: 01020050001079D7
Response: 0102020408BABE