3 master station network schematic, Limitorque actuation systems, Legend – Flowserve DDC-100 Master Station II User Manual

Page 19: Flow control division, Master station ii

Advertising
background image

FCD LMAIM5001-00

DDC-100 Master Station II Installation and Operation Manual

19

Flow Control Division

Limitorque Actuation Systems

4.3

Master Station Network Schematic

Figure 4-4: DDC-100 Redundant Loop Network

Diagnostic Note:

Earth Ground Note:

MOV-3

A2

A2*

A1

A1*

TB5

MOV-247

A1

A1 *

A2

A2*

TB5

N/ C

MOV-249

D-M

D-M*

D-S

D-S*

A1

A1*

A2

A2 *

TB4

TB3

TB5

Notes:

Legend

MOV

D-M

D-M*
D-S

D-S*

N/C

Data terminal is positive with respect to data* terminal

See Note 5

See Note 5

See Note 5

1) Belden 3074F, 3105A, or 9841 shielded cable is recommended.
2) Correct polarity for field unit and network controller

connection is necessary for proper operation.

3) Connections shown are typical. The number of

MOVs shown may not indicate true system size.

4)

Earth ground: ground rod

5)

Earth ground: ground rod or lug in
actuator if actuator is grounded.

Polarity and level of the network’s data connection can
be checked by measuring voltage between data and
data* terminals. This voltage should be greater than
+200mVDC with network controller network ports
disconnected.

If low impedance earth ground is not available at
each actuator, contact engineering for alternative
earth ground surge protection strategies.

A1*

MOV-2

See Note 5

N/C

A2*

N/C

MOV-248

See Note 5

N/C

MOV-4

See Note 5

N/C

16

15

41
29

29
41

D-S

D-S*

D-M

D-M*

TB3

TB4

MOV-1

A2

A2*

A1

A1*

TB5

See Note 5

D-S

D-S*

D-M

D-M*

TB3

TB4

D-M

D-M*

D-S

D-S*

TB4

TB3

15

16

A2

A1

A1*

A2*

29
41

15

16

A2

A1

A1*

A2*

29
41

15

16

A2

A1

Motor-Operated Valve
Data A1
Data A1*
Data A2
Data A2*
Data A1 (UEC-3-DDC)
Data A1*(UEC-3-DDC)

Data A2* (UEC-3-DDC)

Shield

No Connection

Data A2 (UEC-3-DDC)

N/C

MOV-250

See Note 5

A1*

A2*

29
41

15

16

A2

A1

N/C

Channel A

Channel B

MASTER STATION II

Advertising