DDC-100 Master Station II Installation and Operation Manual

FCD LMAIM5001-00

Flow Control Division

Limitorque Actuation Systems

Hot) and allows the user to force the units to switch roles such that the Hot unit becomes the Standby

unit and the Standby unit becomes the Hot unit (Figure 10-3).

Figure 10-2: Configure Hot Standby screen

When configuration changes are saved in the Hot processing unit, these changes are transfered to the

Standby processing unit. Therefore, the network configuration, DCS configuration, and other

configurations only need to be performed once. The configuration for the Hot Standby Parameters are

unique for each processing unit, however, and as such must be completed independently for each

processing unit. The Hot Standby configuration is not transferred from the Hot unit to the Standby unit

when the configuration is saved.

Figure 10-3: Edit Hot Standby screen

Change State

Active/Standby

Configure Hot Standby

Hot Backup State

Idle

Standby

Active

Hot Backup Startup

Hot

Standby

Change State

Active/Standby

Configure Hot Standby

Hot Backup State

Idle

Standby

Active

Hot

Edit

Hot Backup Startup