Limitorque actuation systems – Flowserve DDC-100 Master Station II User Manual

Page 39

Advertising
background image

FCD LMAIM5001-00

DDC-100 Master Station II Installation and Operation Manual

39

Flow Control Division

Limitorque Actuation Systems

Figure 7-10: The Data Coils screen

Available Coils for each MOV

Coil

Bit

Slave

Number

Number

Address

MX-DDC

UEC-3-DDC

I/O Module

1

0

1

Close / Stop

Close / Stop

Do Not Use

2

1

1

Open / Stop

Open / Stop

Do Not Use

3

2

1

AS-1

Lockout / K3

Relay #3

4

3

1

AS-2

Do Not Use

Relay #4

5

4

1

AS-3

Do Not Use

Relay #5

6

5

1

AS-4

K6

Relay #6

7

6

1

AR-1

Do Not Use

Relay #2

8

7

1

AR-2

Do Not Use

Relay #1

9

8

1

AR-3

Do Not Use

Do Not Use

Touching the “<< Back” button will take the user to the coil selection screen where the chosen coil format

may be saved or altered to another configuration. (Figure 7-9).

Note: Once the selection is made, the “Store” button must be pressed for the configuration to be stored.

Selecting a coil for a specific field unit follows the convention listed below.

DCS Requested Coil = [(field unit address –1) * number of coils per unit] + desired coil

06 —Preset Single Register / 16 —Preset Multiple Register

Presets a value into a single-holding register. (16 Presets a value into multiple-holding registers) The data

table for this function code only permits one or two write registers per field unit. A unique data table is

created starting at register 45001.

Touching the “View/Edit” button for Modbus 06/16 will take the user to a screen similar to Figure 7-12.

This screen permits the user to select the MOV parameters for holding register status.

Data Table Modbus Function Code 05

Coil# MOV# Meaning

0001 1 Close

0002 1 Open

0003 2 Close

0004 2 Open

0005 3 Close

0006 3 Open

0007 4 Close

0008 4 Open

0009 5 Close

0010 5 Open

0011 6 Close

0012 6 Open

Coil# MOV# Meaning

<< Back

Advertising