Dcs port configuration – Flowserve DDC-100 Master Station II User Manual

Page 31

Advertising
background image

FCD LMAIM5001-00

DDC-100 Master Station II Installation and Operation Manual

31

Flow Control Division

Limitorque Actuation Systems

7

DCS Port Configuration

7.1

Introduction

DCS Port: includes baud rate for DCS communication, stop bits, parity, electrical standard, DCS address,

RTS ON delay, RTS OFF delay, HMI state during DCS communication traffic, and selectable register maps

for Modbus function code 3, Modbus function code 5/15, and Modbus function code 6/16.

These screens allow the user to configure the DCS port for operation. The first screen presented allows

the user to configure Baud Rate, Retries, Parity, and Electrical connection (Figure 7-1).

Figure 7-1: The Configure DCS Port screen

Touching “Next >>” will take the user to the next DCS Port configuration screen on which the DCS Port

Address, RTS ON Delay, RTS OFF Delay, and HMI control may be disabled when DCS communication

traffic is active (Figure 7-2).

Configure DCS Port

Baud Rate

Stop Bits

Electrical

1

2

RS-232

RS-422

RS-485

None

Even

Odd

Parity

4800

9600

19200

38400

57600

115200

<< Back

Next >>