DDC-100 Master Station II Installation and Operation Manual

FCD LMAIM5001-00

Flow Control Division

Limitorque Actuation Systems

DCS Requested Register = [(field unit address –1) * number of registers per unit] + desired register

Touching the “View/Edit” button for Modbus 05/15 will take the user to a screen similar to Figure 7-9.

This screen permits the user to select desired coils/MOV.

01 —Read Coil Status

Reads the ON/OFF status of discrete outputs (coils) in the field units. This data table is configured with the

Modbus Function code 05/15 parameters.

05 —Force Single Coil / 15 —Force Multiple Coil

Forces only a single coil to either the ON or OFF state (15 Forces multiple coils to either the ON or OFF

state). This is a configurable value.

Figure 7-9: The Force Coils screen

When the users selects the coils to be mapped into the DCS Data table, the toggle switch will display a

green dot. All coils between the first selected toggle switch and the last toggle switch selected will be

displayed. Once the selections have been completed, touching the “View >>” button will display a sample

Data Table for the first 12 coils (Figure 7-10).

Modbus Coils

AS-1

Close/Stop

Select Desired Coils/MOV

Open/Stop

AS-2

AS-3

AS-4

AR-3

AR-2

AR-1

Store

View >>

<< Back

Always

On

Always

On