FCD LMAIM5001-00

DDC-100 Master Station II Installation and Operation Manual

35

Flow Control Division

Limitorque Actuation Systems

03 —Read Holding Registers

Reads the binary contents of holding registers in the field units. The Master Station will allow the user to

select the number of registers to be visible per field unit up to a maximum of 10 (registers 4 – 13). Default

setting will display field unit registers 8 and 9.

Figure 7-7: The Register Selection screen

When the user selects the register(s) to be mapped into the DCS Data table, the toggle switch will display

a green dot. All registers between the first selected toggle switch and the last toggle switch selected will

be displayed. Once the selections have been completed, touching the “View >>” button will display a

sample Data Table for the first 12 registers (Figure 7-8).

Note: Once the selection is made, the “Store” button must be pressed for the configuration to be

stored.

Figure 7-8: The Sample Data Table screen

Touching the “<< Back” button will take the user to the register selection screen where the chosen register

format may be saved or altered to another configuration. (Figure 7-7).

Data Table Modbus Function Code 03

Reg.# MOV# Meaning

40001 1 Pos

40002 1 Status

40003 2 Pos

40004 2 Status

40005 3 Pos

40006 3 Status

40007 4 Pos

40008 4 Status

40009 5 Pos

40010 5 Status

40011 6 Pos

40012 6 Status

Reg.# MOV# Meaning

<< Back

Modbus Holding Registers

Select Desired Registers/MOV

Torque

Volts

Analog #1 Analog #2

D. out

Fault

Status

Position

DI #1

DI #2

Always

On

Store

View >>

<< Back