2 data table configuration – Flowserve DDC-100 Master Station II User Manual

Page 33

Advertising
background image

FCD LMAIM5001-00

DDC-100 Master Station II Installation and Operation Manual

33

Flow Control Division

Limitorque Actuation Systems

Figure 7-4: RTS ON Delay screen

Press Back after editing values.

Figure 7-5: RTS OFF Delay screen

Press Back after editing values.

Touching “Next >>” on the DCS Port Configuration screen will take the user to the next DCS Data Table

Configuration screen.

7.2

Data Table Configuration

The Master Station data table is configurable for the Modbus Function codes 01, 05, 03, 05/15, 06/16.

The Modbus function codes 02 and 04 have a fixed data table and do not permit user alteration

(Figure 7-6).

RTS Off Delay

Current Value:

0

1-65535

Valid Range:

Time delay
(1 ms each incr.)
after the last
char. transmit
and before RTS
is dropped.

0

<< Back

7

8

9

6

5

4

1

2

3

0

.

CLR

DEL

-

E

N

T

RTS On Delay

Current Value:

0

1-65535

Valid Range:

Time delay
(1 ms incr.)
between asserting
RTS and the
transmission of
data.

0

<< Back

7

8

9

6

5

4

1

2

3

0

.

CLR

DEL

-

E

N

T