3 operation, Limitorque actuation systems – Flowserve DDC-100 Master Station II User Manual

Page 53

Advertising
background image

FCD LMAIM5001-00

DDC-100 Master Station II Installation and Operation Manual

53

Flow Control Division

Limitorque Actuation Systems

10.3

Operation

Under normal operating conditions, the Hot processing unit will transmit incremental data updates to the

Standby processing unit via the Ethernet connection.

The Standby unit will also monitor the communication on the network to ensure that the Hot processing

unit is viable.

In the event of a Hot unit failure, the Standby unit will smoothly transition into the Hot role. In addition, a

forced switch may be imposed. The transition period from Hot to Standby and Standby to Hot takes under

20 milliseconds to complete.

Each processing unit is capable of three states: Idle, Standby, and Hot.

Idle state: the processing unit is active, will accept incremental updates from a Hot unit, but will not perform

the Hot unit’s duties nor will the processing unit switch to Hot state should a Hot failure be detected.

Standby state: the processing unit is active, will accept incremental updates from a Hot unit, and will

switch to Hot state should a Hot failure be detected.

Hot state: the processing unit is the Hot unit and will perform the Hot duties of Network polling and

incremental updating of the Standby processing unit.

A state change can occur in any of the following conditions:

Hot Unit Failure: the Hot unit fails to send incremental updates to the Standby unit and there is no

network traffic.

Hot-Standby communication failure: the Standby unit is not receiving incremental update information

from the Hot unit but detects Network traffic. The Standby unit will zero its database and set an alert error.

The HMI will detect this state and will display “Idle” instead of “Standby”.