9 network wiring – profibus dp/pa installation, 10 network wiring – devicenet – Flowserve MX Electronic Actuator User Manual

Page 30

Advertising
background image

Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

30

3.3.9 Network Wiring – Profibus DP/PA Installation

Profibus DP is based on RS 485 communication. The standard EN 50170 specifies the cable for use with Profibus DP.

The following specifications need to be fulfilled by the Profibus cable:

Table 3.6 – Profibus cable specifications

Parameter

Type – Profibus DP

Impedance

135 to 165 ohm/3 to 20 MHz

Capacity

< 30 pF/m

Resistance

< 110 ohm/km

Wire gauge

> 0.64 mm

Conductor area

> 0.34 mm

2

The Profibus DP cable is a shielded twisted pair cable.

In general, there are two different types of cables available. The most commonly used cable has solid wire for the
Profibus line. When there is a need for more flexiblity (bending) and higher environmental resistance, a cable with
stranded wire for the Profibus line and special jackets shall be used. Limitorque recommends the use of:

• Belden 3079A Specifications, 22 AWG, shielded, solid two conductor

Key Specifications
• Capacitance/ft = 8.5 pF
• Nominal Impedance (ohms) – 150.0

Network Wiring - Profibus PA
Please refer to IEC 61158 & ANSI/ISA S.50.02 Part 2-1992 for network wiring guidelines. Refer to Table 3.5 for
connections.

3.3.10 Network Wiring – DeviceNet

DeviceNet is a CAN-based protocol that uses five wires including a shield. Two of the conductors are used for 24 VDC
power and up to 8 amps (4 amps for NEC Class 2) may be passed along the hi-way from a suitable power source. Two
conductors are used for the CAN bus signals, CAN_H and CAN_L, which are usually smaller in diameter. Flowserve
recommends Belden 3082A cable for connecting to a DeviceNet network. The specifications for this cable are preferred.

Table 3.7 – DeviceNet cable specifications

Belden

Part No.

AWG (Stranding)

dia. Inches

Nom. DCR

Insulation

material

(color code)

Nominal

O.D.

Nom

Impedance

(ohms)

Nominal

Capacitance

Test

Frequency

(MHz)

Maximum

Attenuation

dB/100ft

3082A

2 – 15 AWG (19 x 28)

3.6 ohm/1000 ft

11.8 ohm/km

Power pair

(Black/Red)

12.2 mm

120

12.0 pF/ft

0.125

0.5

1

0.13

0.25

1.36

2 – 18 AWG (19 x 30)

6.9 ohm/1000 ft

22.7 ohm/km

Data pair

(Blue/White)

3084A

2 – 22 AWG (19 x 34)

17.5 ohm/1000 ft

57.4 ohm/km

Power pair

(Black/Red)

7.2 mm

120

12.0 pF/ft

0.125

0.5

1

0.29

0.50

1.70

2 – 18 AWG (19 x 36)

28.0 ohm/1000 ft

91.9 ohm/km

Data pair

(Blue/White)

Advertising
This manual is related to the following products: