10 ff option – Flowserve MX Electronic Actuator User Manual

Page 52

Advertising
background image

Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

52

4.9.6 Proportional Band

Proportional band is the range of errors between position and demand signal that will produce reduced speed (pulsing).

Default = 15%

To change from the default, select “NO” until the required value is displayed. The value is adjustable between 1% and
100%, in 1% increments.

4.9.7 Deadband

Default = 2%

The deadband should be wide enough to prevent “hunting” of the actuator but as low as possible to give adequate
response to changes in the error signal.

To Change from the Default Range:
Select “NO” to adjust the value between 0.5% and 50%, in 0.5% increments to suit the application.

4.9.8 Offset

Default = 4 mA/20 mA

No options are available. Select “YES.”

0-10 VDC is available on all units shipped after 6/01/03.

4.9.9 Move To

If positioning is selected as an action, then the Move To dialog will appear. Position is configurable from 0-100%.

4.9.10 Comm Loss Delay

Default = 60 sec.

The User may select the amount of time delay before communication loss is flagged to the network. This selection is
configurable from 120 seconds.

4.9.11 Comm Loss Action

Default = None

The User may select what action the actuator should take when network communication is interrupted. This action is
configurable as Close, Open, Stop, Position.

4.10 FF Option

FF option enables the actuator to be controlled by a Foundation Fieldbus communications signal. If the option has been
purchased, it is automatically enabled. A Fieldbus System configuration tool must be used by the customer to set the FF
address.

NOTE: If the FF option has not been purchased, the screens for changing FF will not be available. To add the FF option,
please consult Limitorque service at (434) 528-4400.

The MX is equipped with the ability to either hardwire to digital inputs for control, set-up for analog control (Modutronic),
or control via network protocols. In order to utilize this feature, then select “Multi-control mode” operation located in
Section 4.16, Remote Mode. This is the default setting for remote control. There are three modes of remote control
when remote mode is configured for multi control: digital control, analog control, and network control. Digital and
network control operation is based on the last command received. Analog operation is initiated by either toggling user
input 2 (configure for CSE input) or breaking and reapplying the analog control.

Advertising
This manual is related to the following products: