1 status, 2 pb dp operation, Figure 4.15 – profibus dp – Flowserve MX Electronic Actuator User Manual

Page 55

Advertising
background image

55

Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

flowserve.com

Figure 4.15 – Profibus DP

4.11.1 Status

Default = ON

PB Status enables user to change from the default condition to turn on and off the digital control capability of the actuator.

4.11.2 PB DP Operation

Figure 4.15 illustrates the setup sequence for the MX/QX PB DP field unit. For proper operation, either Position Mode or
Open/Close Mode must be selected.

Follow these steps to enter and configure the setup mode:

1. Proceed through the Setup to the CHANGE PBDP? display.

2. Select YES to proceed to the PBDP-A STATUS (ON)-OK? display. PBDP-A Status enables the user to change from

the default condition to turn on and off the digital control capability of the actuator.

3. Select YES to proceed to the PBDP-B STATUS (ON)-OK? display. PBDP-B Status enables the user to change from

the default condition to turn on and off the redundant digital control capability of the actuator, if installed.

4. Select YES to proceed to the REDUNDANT MASTER (YES)-OK? display. Selecting REDUNDANT MASTER will allow

for System Redundancy with two independent connections to Profibus masters. REDUNDANT MASTER must be
set to NO for Flying Redundancy (single Profibus master connection).

5. If YES is selected, MONITOR STANDBY PB (ON)-OK? is displayed.

6. To allow the standby Profibus master to monitor the health of the actuator’s standby PB DP board, select YES.

7. The unit will display PB ADDRESS 1–OK? If OK, select YES. If NO, select different address (1-125).

8. Select YES to proceed to the ANALOG SCALE display.

9. From ANALOG SCALE, if the default value of 0-100 is OK, select YES. If not, select NO.

10. If YES is selected, ESD ACTION (IGNORE) – OK? is displayed.

11. For ignoring ESD ACTION, select YES. For setting ESD ACTION, select NO. If POSITION is chosen as action, ESD

MOVE TO (XXX%)-OK? is displayed. Select NO to set desired position.

*

YES

NO

CHANGE

PB/DP?

YES

NO

PBDP-A STATUS

(ON)-OK?

YES

NO

PBDP-B STATUS

(ON)-OK?

YES

NO

MONITOR STANDBY

PB (ON)-OK?

YES

NO

(0-125)

Unit increments

PB ADRESS1

OK?

YES

NO

(0-255)

(0-4095)

ANALOG SCALE

0-100-OK?

YES

NO

REDUNDANT

MASTER (YES)-OK?

YES

NO

(CLOSE)

(OPEN)

(STOP)

(POSITION)

COMMLOSS ACTION

(NONE)-OK?

YES

NO

(0-100%)

ESD MOVE TO

(XXX%)-OK?

YES

NO

(0-4095)

COMMLOSS DELAY

60 SECS-OK?

YES

NO

(CLOSE)

(OPEN)

(STOP)

(POSITION)

ESD ACTION

(IGNORE)-OK?

*

YES

NO

(0-100%)

MOVE TO

(XXX%)-OK?

YES

NO

OPEN/CLOSE

MODE-OK?

YES

POSITION

MODE-OK?

YES

NO

CHANGE PROP/

DEAD BAND?

YES

NO

(1%-100%)

1% Increments

PROP BAND

(15%)-OK?

YES

NO

(1%-50%)

1% Increments

DEADBAND

(2%)-OK?

* If POSITION is chosen, as action,

this menu will appear.

Advertising
This manual is related to the following products: