Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

90

---% OPEN, TORQUE TIMEOUT – The torque switch timed out after the actuator determined that it has reached its

torque seat

“SET LIMITS” – Normal display if red selector knob is in “LOCAL” or “REMOTE” and position limits have not been set

“INITIALIZE” – “INITIALIZE” will be displayed if module has no actuator configuration. No operation will be permitted
until initialization has been completed. Refer to “ROM ERROR” for routine on next page. See Figure 5.1.

“ANALOG OUT 1 LOSS” – Analog board output-driver chip is reporting a fault, and cannot be reset; resulting in loss of
analog out signal.

“ANALOG OUT 2 LOSS” – Analog board output-driver chip is reporting a fault, and cannot be reset; resulting in loss of
analog out signal.

RAM Error
The MX processor continually checks RAM for memory corruption errors. If corruption is detected, the processor will
force a reset to clear RAM. The LCD will temporarily display the following prior to this reset:

“XXX% OPEN”

“RAM ERROR”

After the reset, the display will read normally. Any momentary commands (DDC command, momentary pushbutton,
etc.) that were not completely executed must be reissued.

ROM Error
The MX processor continually checks EPROM for memory corruption errors. If corruption is detected, operation is
disabled. If the selector switch is in “LOCAL” or “REMOTE,” the LCD will display the following:

“XXX% OPEN”

“ROM ERROR”

When the selector is placed in “STOP,” the unit will require reinitialization and the LCD will display the following dialog:

Figure 5.1 – Initialize routine

YES

NO

NO

YES

NO

YES

YES

YES

NO

NO

YES

NO

UNIT SIZE

MX-05-OK?

VOLTAGE

460 VOLT-OK?

Hz

60 Hz-OK?

ACTUATOR RP M

12/18-OK?

S/N

0------OK?

COLD (-60°C) UNIT

YES/NO -OK?

INITIALIZE?

Answer “

NO ” until the

correct unit size is

displayed. Refer to

nameplate.

Answer “

NO ” until

the correct voltage

is displayed. Refer

to nameplate.

Answer “

NO ” until

the correct frequency

is displayed. Refer to

nameplate.

Answer “

NO ” until

the correct rpm

is displayed. Refer

to nameplate.

Answer “

NO ” until the

value is displayed and

then “

YES ” to enter .

Refer to namplate for

S/N.

Answer “

NO” to

select normal

temperature

parameters,

-22°F to +158°F

(-30°C to +70°C).

Answer “

YES” to select arctic

temperature parameters,

-76°F to +140°F (-60°C to

+60°C).

Please refer to Limitorque

MX Customer Connection(s) Diagram

reverse side (located on the

inside of the terminal compartment

cover) for customer default

configuration.

Answer

NO” to

change.

Answer “

YES

to save settings.

NO

YES