18 esd (emergency shutdown) overrides, 2 led customization, 1 esd override – Flowserve MX Electronic Actuator User Manual

Page 69

Advertising
background image

69

Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

flowserve.com

• Maintain mode: the unit will operate continually in either direction when the black knob is actuated and released, until

the position of the black knob is changed or the red knob is changed from “LOCAL” to either “STOP” or “REMOTE.”

• Inching mode: the unit will operate only when the black knob is held in the open or close position. If the black knob is

released, the unit will stop.

To Customize the Settings:
1. Select “CHANGE LOCAL CONTROL?” from the “SETUP” routine.

2. Select “YES” to enter the mode display.

3. Select “NO” to change from Maintain to Inching control.

4.17.2 LED Customization

This selection allows the customer to reverse the colors of the LED in open and close mode from the default setting.

Default = Red-Open/Green-Close

1. After mode selection, select “YES” to change the colors of the LEDs.

2. Select “NO” to change from the default to Red-Close/Green-Open.

4.18 ESD (Emergency Shutdown) Overrides

An external contact may be used to place the actuator in emergency shutdown mode. An ESD contact may be
connected to the actuator to override existing command signals and send the valve to a predetermined position.

The ESD Action and Signal presence is selected in Section 4.19, Inputs. The default ESD input = Input 0., pt. 30 on
wiring diagram.

4.18.1 ESD Override

It may be desirable that ESD override other events. These events are selectable. The “>” symbol after ESD indicates that
ESD will override that particular event. Sections 4.19 - 4.25, Inputs through Motor Thermostat list the choices.

Figure 4.28 – ESD overrides

YES

YES

YES

NO

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

NO

NO

NO

NO

NO

NO

NO

*

*

*

* CAUTION: The user may select “ESD” to

override these situations. Should these

conditions occur and the user has

selected “ESD>,” be advised that

the actuator motor may be compromised

Therefore, selection of “ESD>

in these situations will void the

warranty and certification.

*

CHANGE

ESD OVERRIDES?

PRIORITY

INHIBIT>ESD

PRIORITY

LOCAL CMD>ESD

PRIORITY

STOP>ESD

PRIORITY

JAMMED>ESD

PRIORITY

LOST PHASE>ESD

PRIORITY

OVERTORQUE>ESD

PRIORITY

INHIBIT<ESD

PRIORITY

LOCAL CMD<ESD

PRIORITY

STOP<ESD

PRIORITY

ESD>JAMMED

PRIORITY

ESD>LOST PHASE

PRIORITY ESD>

OVERTORQUE

PRIORITY

NW ESD>LOCAL ESD

PRIORITY

*

YES

YES

NO

PRIORITY

THERMOSTAT>ESD

PRIORITY

ESD>THERMOSTAT

*

YES

YES

YES

NO

PRIORITY

2SPD > ESD

PRIORITY

ESD > 2SPD

*

LOCAL ESD>NW ESD

YES

YES

NO

PRIORITY

OIL OVERTEMP>ESD

PRIORITY

ESD>OIL OVERTEMP

*

YES

YES

NO

PRIORITY

TORQUE TIMER>ESD

PRIORITY

ESD>TORQUE TIMER