Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

80

Table 4.1 – Digital input terminals

Negative Switching (Positive Earth)

Mode

Input 0

Input 1

Input 2

Input 3

Input 4

Input 5

2-wire

configurable

open

not used

configurable

not used

not used

3-wire inch

close

open

not used

configurable

not used

not used

3-wire maint

close

open

not used

configurable

not used

not used

4-wire

close

open

not used

stop

not used

not used

User Input

configurable

configurable

not used

configurable

not used

not used

Terminal connections
Input 0

Input 1

Input 2

Input 3

Input 4

Input 5

+VDC

-VDC

+VDC -VDC

+VDC -VDC

+VDC -VDC

+VDC

-VDC

+VDC

-VDC

30

32

34

29

N/A

N/A

26

28

N/A

N/A

N/A

N/A

Custom Modes

Mode

Input 0

Input 1

Input 2

Input 3

Input 4

Input 5

1

not used

PS Enable 1

PS Enable 2

ESD Release 2

ESD Release 1

MO ESD/PSESD

2

stop

close

open

ESD Release 2

ESD Release 1

MO ESD

3

ESD TDR

configurable

configurable

stop

open

close

(MO - momentary signal)
4

M1 Position

M2 Position

configurable

stop

open

close

Terminal connections
Input 0

Input 1

Input 2

Input 3

Input 4

Input 5

+VDC

-VDC

+VDC -VDC

+VDC -VDC

+VDC -VDC

+VDC

-VDC

+VDC

-VDC

30

32 or 33 34

29 or 31 35

29 or 31

26

28

25

28

27

28

Jumpers can be used to connect the digital commons as needed. 28 to 29, 31 to 32, 33, to VDC source common.

Limigard Mode

Mode

Input 0

Input 1

Input 2

Input 3

Input 4

Input 5

close

open

stop

stop

open

close

Sil Modes

Mode

Input 0

Input 1

Input 2

Input 3

Input 4

Input 5

Standard

ESD

Partial Stroke Test configurable

stop

open

close

Enhanced

configurable

PS Enable 1

PS Enable 2

ESD Release 2

ESD Release 1

MO ESD/PSESD