7 view identification, 8 view torque profile – Flowserve MX Electronic Actuator User Manual

Page 93

Advertising
background image

93

Limitorque MX Electronic Actuator FCD LMENIM2306-06 – 10/13

flowserve.com

5.7 View Identification

In this dialog, the identity of the actuator may be reviewed. This dialog provides valuable information for the ordering of
spare parts or checking the specification of the actuator.

NOTE: The serial number, order number, and software revision number were entered at the time of manufacture and
cannot be changed on screen. The software revision number is necessary when option boards are ordered.

Figure 5.6 – View identification

YES

YES

YES

NO

NO

YES

NO

NO

YES

NO

VIEW

IDENTIFICATION?

TAG #

MOV257

SERIAL #

M002567

ORDER #

366765F

FIRMWARE REV.

E654

YES

YES

NO

NO

YES

NO

YES

NO

VIEW NETWORK

REVISIONS?

YES

NO

DDC MODBUS

XXXXXXX

FF REV

XXXXXXXX

YES

NO

PROFIBUS DP

XXXXXXXX

PROFIBUS PA

XXXXXXXX

DEVICENET

XXXXXXXX

*Network revisions will only be displayed if the optional network board is installed within the MX.

*

*

*

*

-OK?

-OK?

-OK?

5.8 View Torque Profile

The information contained in the “TORQUE PROFILE” dialog provides indication of the condition of the valve relative to
the last time that the “DIAGNOSTIC RESET” reference values were reset. See Section 4.22, TAG Number. It can give an
indication of a change in the process conditions, such as an increase in pressure.

Details are given for the REFERENCE and the LAST torque, expressed as a percentage of the rated torque (stated on
the nameplate, Figure 4.7) that occurred at BREAKOUT, ENDING, and PEAK RUNNING for both the opening and closing
directions. Torque will be expressed proportionally as a reference only from 40% to 100% inclusive. Initial indication
may read 0% until torque exceeds 40% minimum.

• “BREAKOUT” – Amount of torque required to unseat the valve.
• “ENDING” – Amount of torque required to seat the valve.
• “PEAK RUNNING” – Maximum torque detected while cycling from BREAKOUT to ENDING. (Maximum mid-travel

torque.)

Figure 5.7 – View torque profile

YES

YES

YES

NO

NO

YES

YES

NO

NO

NO

YES

NO

YES

NO

YES

YES

YES

NO

NO

YES

YES

NO

NO

NO

YES

NO

YES

NO

YES

VIEW

O PEN D IRECTION?

B REAKOUT-REF

65(%)-NEXT?

BREAKOUT-LAST

70(%)-NEXT?

PEAK RUN

REF 40(%)-NEXT?

ENDING-LAST

40(%)-EXIT?

PEAK RUN

LAST 40(%)-NEXT?

ENDING - REF

40(%)-NEXT?

VIEW

CLOSE D IRECTION?

B REAKOUT-REF

40(%)-NEXT?

BREAKOUT-

LAST 43(%)-NEXT?

PEAK RUN

REF 40(%)-NEXT?

ENDING-LAST

60(%)-EXIT?

PEAK RUN

LAST 40(%)-NEXT?

ENDING-REF

55(%)-NEXT?

VIEW

TORQUE PROFILE

Advertising
This manual is related to the following products: