12. If YES is selected, COMM LOSS ACTION (NONE) – OK? is displayed.

13. For no COMM LOSS ACTION, select YES. For setting COMM LOSS ACTION, select NO. If POSITION is chosen,

as action, COMM LOSS MOVE TO (XXX%)-OK? is displayed. Select NO to set desired position.

14. If YES is selected, COMM LOSS DELAY (60 SEC) – OK? is displayed.

15. For a 60-second delay, select YES. Otherwise, select NO until the required value is displayed.

16. If YES is selected, OPEN/CLOSE MODE-OK? is displayed.

17. For OPEN/CLOSE MODE, select YES. For POSITION MODE, select NO. In position mode, the host device can set

the valve position to any desired value; in OPEN/CLOSE MODE the host can only fully open or fully close the valve.
The user must locally configure one of these two modes.

18. Proceed to configure the proportional band and deadband as discussed in the next sections.

4.11.3 Comm Loss Delay

Default = 60 sec.

The User may select the amount of time delay before communication loss is flagged to the network. This selection is
configurable from 120 seconds.

4.11.4 Comm Loss Action

Default = None

The User may select what action the actuator should take when network communication is interrupted. This action is
configurable as Close, Open, Stop, Position.

Figure 4.16 – Profibus PA

NO

(OFF)

YES

NO

NO

NO

YES

YES

YES

YES

(1%-100%)

1% Increments

(1%-50%)

1% Increments

CHANGE

PB/PA?

STATUS

(ON)-OK?

YES

CHANGE PROP/

DEADBAND?

NO

YES

DEADBAND

(2%)-OK?

PROP BAND

(15%)-OK?

NO

OPEN/CLOSE

MODE-OK?

POSITION

MODE-OK?

NO

YES

NO

YES

PB ADDRESS

(1)-OK?

(1-125)

Unit Increments

(CLOSE)

(OPEN)

(STOP)

(POSITION)

YES

NO

ESD ACTION

(IGNORE)-OK?

(CLOSE)

(OPEN)

(STOP)

(POSITION)

YES

YES

NO

COMM LOSS ACTION

(NONE)-OK?

(0-4095)

NO

COMM LOSS DELAY

(60 SEC)-OK?

(0-100%)

*

*

YES

NO

MOVE TO

XXX% OPEN

(0-100%)

YES

NO

MOVE TO

XXX% OPEN

* If POSITION is chosen, as action,

this menu will appear.

ANALOG SCALE

0-100-OK?