Pump #x disabled, no price, Pump #x enabled, Pump control unit #x came up – Gasboy CFN III Manager Manual V3.6 User Manual

Page 291: Pump control unit #x disabled, Pump control unit #x down, bad memory, Pump control unit #x found unassigned transaction, Pump # x disabled, no price, Pump # x enabled, Pump control unit # x came up, Pump control unit # x disabled

Advertising
background image

MDE-4871 CFN III Manager’s Manual for Windows® XP Embedded - Version 3.6 · August 2010

Page D-9

Messages on the Log Printer

Status and Error Messages

To re-enable a pump that has been disabled because of too many zero-quantity transactions,
after first identifying and correcting the cause, type the command ENABLE PUMP.

To reset the NQN counters for all pumps back to zero, give the command ENABLE PUMP;I.
Wait until no fuel transactions are in progress.

Pump #X Disabled, No Price

The SC III has disabled the pump because no price or price code has been assigned for that
pump.

Use PRINT PUMP to determine if a price code has been assigned to the pump. If one has, then
use PRINT PRICE to see if a price has been assigned to that code for level 0 and for the level
for each method of payment that is accepted. If a price is missing for that code or for some
required level, use LOAD PRICE to load it.

If no price code has been assigned to the hose, then use LOAD FUEL to assign a price code to
the pump. (Some sites may choose to assign a product that has a price to the pump instead of a
price code, if multi-level prices for cash, credit, etc., are not required.)

Pump #X Enabled

The indicated pump is operating normally.

No action is required.

Pump Control Unit #X Came Up

The indicated pump control unit is now functioning properly.

No action is required.

Pump Control Unit #X Disabled

The indicated pump control unit has been disabled by the command DISABLE PCU.

No action is required. Use the command ENABLE PCU to return the pump control unit to
operation, when appropriate.

Pump Control Unit #X Down, Bad Memory

The indicated pump control unit is not functioning because of a memory failure.

Call your service representative.

Pump Control Unit #X Found Unassigned Transaction

The SC III received unexpected information from the indicated pump control unit. This is
recorded as an unpaid transaction.