Evaporative cooling with recirculating pump – Greenheck DG / DGX with Direct Spark (464043 IOM) (Pre-2008) User Manual

Page 12

Advertising
background image

12

Installation - Evaporative Cooling Piping (Optional)

Evaporative Cooling with Recirculating Pump

Installation

IMPORTANT!

The supply line should be of adequate size and pressure to resupply the amount of water lost due to

bleed-off and evaporation. The drain line should be the same size or larger than the supply line.

Step 1 Install the Water Supply Line

Supply line opening requirements vary by unit size and arrangement and are field supplied. Connect the water
supply line to the float valve through the supply line opening in the evaporative cooling unit. Install a manual
shutoff valve in the supply line as shown above.

Step 2 Install the Drain Line

Connect an unobstructed drain line to the drain and
overflow connections on the evaporative cooler. A
manual shut off valve (by others) is required for the
evaporative cooler drain line. A trap should be used
to prevent sewer gas from being drawn into the unit.
Refer to piping diagram above.

Step 3 Check/Adjust Water Level

Check the water level in the sump tank. The water
level should be above the pump intake and below the
overflow. Adjust the float as needed to achieve the
proper water level.

CAUTION!

Provisions must be taken to prevent damage to the evaporative cooling section during freezing

conditions. The sump, drain lines and supply lines must be drained prior to freezing conditions or an

alternate method must be used to protect the lines and media.

IMPORTANT!

All supply solenoids, valves and all traps must be below the roofline or be otherwise protected from

freezing.

6 in. min.

6 in. min.

Supply Line

Overflow

Trap

Drain Line Valve
(Normally Open)

Drain Line

Supply Line Valve
(Normally Closed)

Recirculating Evaporative Piping

Drain Trap

Advertising
This manual is related to the following products: