Installation

Evaporative Cooling with the Water Wizard

Installation - Water Wizard™ (Optional)

Step 3 Wire the Solenoid(s)

Wire the supply line solenoid and drain solenoid as
shown on the unit’s wiring diagram in the control
center.

Step 4 Wire the Temperature Sensor

If the evaporative cooler shipped separate from the unit, the temperature sensor must be wired. The sensor wire
is bundled inside the discharge end of the evaporative cooler. Wire the sensor wire to terminals AI2 and AIC on
the terminal strip in the unit’s control center.

Step 1 Install Normally Closed Supply Line/Solenoid

Connect the water supply line to the manual supply valve in the unit. Install the supply solenoid in the supply
line, upstream of the manual supply valve and below the roofline.

Step 2 Install Normally Open Drain Line/Solenoid

Connect the drain line to the supply line between the manual supply valve and the supply solenoid. Install a
drain solenoid in the drain line, below the roof line. A trap should be installed in the drain line.

CAUTION!

Any wiring deviations may result in personal
injury or property damage. Greenheck is not

responsible for any damage to, or failure of the

unit caused by incorrect final wiring.

NOTE!

The Water Wizard start-up must be completed for proper performance.

NOTE!

Solenoid(s) may be provided by Greenheck (if ordered) or by others.

WARNING!

Disconnect and lock-out all power and gas

before performing any maintenance or service to

the unit. Failure to do so could result in serious

injury or death and damage to equipment.

NOTE!

The following instructions are provided for

evaporative coolers equipped with the Water

Wizard only. Additional instructions are provided

for evaporative coolers equipped with the auto-

drain and fill or bleed-off.

Water Wizard Valves (when provided by Greenheck)

Unit

Model

Assembly

Number

GFC

Part Number

ASCO

Part Number

Solenoid

Type

De-Energized

Position

Diameter

Quantity

DG0H10/H20

DGX-H12/H22

DGX-H30 (<9000 cfm)

852370

461262

8210G2

Supply

Closed

1/2 inch

1

383086

8210G34

Supply Line

Drain

Open

1/2 inch

1

DG-H30

DGX-H32 (9000 cfm)

852371

383088

8210G9

Supply

Closed

3/4 inch

1

383086

8210G34

Supply Line

Drain

Open

1/2 inch

1

Supply Line Drain Solenoid

(Normally Open)

Supply Solenoid

(Normally Closed)

Manual

Supply Valve

Pressure

Gauge

To Media

Sump

Drain

Roof

Line

Trap

Water Wizard Installation

Factory

Installed

Field

Installed

Part numbers subject to change.