27

NOTE!

The minimum cooling temperature is preset to the factory recommended 75ºF. Steps 5-7 should only

be complete if the minimum cooling temperature needs adjustment.

NOTE!

The inlet air sensor function overrides and shuts down the evaporative cooler if the outside

temperature falls below the minimum cooling temperature.

Step 5 Enter Program Mode

Press and hold the Enter Key for three

seconds. The display will read “Pro” when

Program Mode is active.

Start-Up - Water Wizard (Optional)

NOTE!

The manual supply valve ships closed and must be

adjusted for proper performance.

Step 2 Set the Water Pressure

With the solenoid open, set the supply water
pressure to the correct setting. (see table at

right). Use the manual supply valve to adjust the
supply pressure. A pressure gauge is provided
between the manual supply valve and the media.

Step 3 Close Solenoid

With the pressure set, press the Function Key
for one second to deactivate Flow Test Mode

and allow the supply solenoid to close.

Step 4 Check Media

Start the cooling cycle and check the media after one
hour of operation. If the media is continuously dry or if
too much water is draining from the sump tank, refer
to Troubleshooting, Water Wizard.

Step 1 Open the Solenoid

Confirm that the manual water supply valve is
closed. Press and hold the Function Button for

one second. L3 will begin blinking (short on, long off),
indicating that Flow Test Mode is active and the
supply solenoid is open.

Program Display

Drain Solenoid

Supply

Solenoid

Manual

Supply Valve

Pressure

Gauge

To Media

Sump

Drain

Roof

Line

Trap

Water Wizard Installation

Start-Up

Recommended Water Pressure Chart

Housing

Size

Media Width

(inches)

Water Pressure

(in. wc)

12

30

20

22

43

3

4

*

36

60*

61

32

66*

72

96*

42

DG-10

26

3

4

19

DG-20

66

74

DG-30

84*

35

*Multiple media sections. Value represents total media width.