Troubleshooting, Blower does not operate – Greenheck DG / DGX with Direct Spark (464043 IOM) (Pre-2008) User Manual

Page 33

Advertising
background image

33

Troubleshooting

115 Vac across

terminals 102 and 101?

Check Main Voltage

(See Blower Start-Up Step #1)

Main Disconnect (DS1) Off

(Turn Main Disconnect DS1 On)

Primary Fuses Blown

(Replace Fuses)

Main Transformer Defective

(Replace Transformer)

24 Vac across

terminals R and X?

Main Transformer Defective

(Replace Transformer)

24 Vac across

terminals 5 and X?

24 Vac across

terminals 4 and X?

24 Vac across

terminals G and X?

Supply Switch (S2) Off

(Turn Supply Switch S2 On)

Fire system contact (FSC) tripped

(Correct/Replace)

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Note: At this time the supply contactor (ST1) should pull in passing

power to the supply motor and the blower should start.

Yes

Blower Does Not Operate

Broken Fan Belt

(Replace - Reference maintenance section)

Defective motor or capacitor

(Repair/Replace)

Blown Motor Fuse

(Replace)

One or more legs of 3 phase is out

(Restore missing legs)

Troubleshooting

24 Vac across

terminals 3 and X?

Supply Fan Overload (ST1 OL) Tripped

(Reset and check motor amps, reference Blower Start-Up #4)

Damper Limit Switch (DL1) Holding

(Wait for actuator to open fully or adjust limit switch)

Damper Limit Switch Jumper Missing

(Install jumper, reference the units ladder diagram for terminals)

Optional Exhaust Fan Interlocks (ST2-ST5) Open

(Correct/Replace)

Freeze Protection (FZ) Tripped

(Reset)