Step 1 Check the Supply Gas Pressure

Check the supply gas pressure and compare it with the unit’s nameplate pressure requirements. Adjust the
supply regulator as needed until the supply gas pressure is within the specified range. See figure #40. The
nameplate is located on the outside of the unit on the control panel side.

Start-Up

IMPORTANT!

For proper unit function and safety, follow the

start-up procedure in the exact order that it is

presented.

“W.C.

“W.C.

“W.C.

F

PSI

“W.C.

“W.C.

MAX BTU/HR
BTU/H MAX

NORMAL MANIFOLD
PRESSURE
PRESSION D’ADMISSION
NORMALE

MIN GAS
PRESSURE
PRESSION DE GAZ

MIN BURNER
PRESSURE DROP
PERTE MIN DE PRESSION
DANS LE BRULEUR

TYPE OF GAS
NATURE DU GAZ

MIN BTU/HR
BTU/H MIN

MIN GAS PRESSURE
FOR MAX OUTPUT
PRESSION DE GAZ MIN
POUR PUISSANCE MAX

MAX BURNER
PRESSURE DROP
PERTE MAX DE PRESSION
DANS LE BRULEUR

MAX GAS
PRESSURE
PRESSION DE GAZ
MAX

DESIGN ∆T
∆T NORMALE

EQUIPPED FOR

CONCU POUR

SCFM

“W.C.

EXTERNAL STATIC PRESSURE

PRESSION STATIQUE EXTERIEURE

AGAINST

CONTE

Minimum and

maximum gas

pressures for

maximum output

IMPORTANT!

This start-up should begin after all of the

installation procedures and the Blower start-up

have been completed.

Start-Up - Direct Gas

Step 2 Check the Optional High and Low Gas Pressure Switches

Check the settings on the high and low gas pressure switches. The high pressure setting is typically 8 inches wc
and the low pressure is setting is typically 3 inches wc. The switches are set at the factory and should not need
adjustment. Adjust the setting only if needed. See the gas train layout diagram in the reference section for the
high and low pressure switch location.

NOTE!

The purpose of the high and low gas pressure switches is to automatically shut down the burner if the

inlet gas pressure is too low for the burner to safely light, or if the manifold pressure is too high for

the burner to operate properly.