Step 8 Flame Signal Check

To measure the flame signal connect a micro amp
meter to terminals (FC+) and (FC-) on the Fenwal
flame safe guard. The flame signal should be above
1.0 micro amp and steady.

Check the flame signal with the burner at minimum
fire, mid-fire and high-fire.

NOTE!

If the flame signal is not above 1.0 micro amp

and steady, consult the troubleshooting section.

Start-Up - Direct Gas

Step 7 Set the Unit’s Operating Temperature

Set the operating temperature. The operating temperature setting depends on which Maxitrol controller is used.

Maxitrol Series 14

Set the discharge

temperature

(65°F Typical)

IMPORTANT!

The Maxitrol Series 14 should be set to the

desired discharge temperature. The

temperature selector may be built into the

amplifier or may be a stand-alone dial. The

stand-alone dial may be mounted remotely.

Maxitrol Series 44

IMPORTANT!

The Maxitrol Series 44 should be set to the

desired temperature. If the Maxitrol 44 is

provided with the space temperature control

option, the Selectra Stat must be mounted in the

space being heated.

Set the space

temperature

(70°F Typical)

Start-Up

Series 14 Discharge Temperature Setting

Series 44 Temperature Setting

(shown as Space Temperature Control)

Flame Safe Guard

FC+

FC-