Installation - Evaporative Cooler Piping (Optional)

Installation

IMPORTANT!

The supply line should be of adequate size and pressure to resupply the amount of water lost due to

bleed-off and evaporation. The drain line should be the same size or larger than the supply line.

CAUTION!

All solenoids valves and traps must be installed

below the roof to protect the supply water line

from freezing. If they cannot be installed below

the roof, an alternative method must be used to

protect the lines from freezing

IMPORTANT!

The supply solenoid (Valve A) is NOT the same as

the drain solenoids (Valve B and Valve C). Make

sure to use the proper solenoid for each

location. Check you local code requirements for

proper installation of this type of system.

Step 1 Install the Water Supply Line

Supply line opening requirements vary by unit size and arrangement and are field supplied. Connect the water
supply line to the float valve through the supply line opening in the evaporative cooling unit. Install the 1/2 in.
normally closed solenoid (Valve A) in the supply line as shown above. Install the 1/4 in. normally open solenoid
(Valve B) between the supply line and the drain line as shown above.

Step 2 Install the Drain Line

Connect an unobstructed drain line to the sump drain
overflow connection. Install the 3/4 in. normally open
solenoid (Valve C) between the sump drain connection
and the drain line. A trap should be used to prevent
sewer gas from being drawn into the unit. Refer to piping
drawing above.

Evaporative Cooling with Auto Drain and Fill

Step 3 Check/Adjust Water Level

Check the water level in the sump tank. The water level
should be above the pump intake and below the overflow.
Adjust the float as needed to achieve the proper water level.

6 in. min.

6 in. min.

Auto-Drain and Fill Evaporative Piping

Drain Trap

Auto Drain & Flush Valves (when provided by Greenheck)

Assembly

Number

GFC

Part Number

ASCO

Part Number

Solenoid Type

De-Energized

Position

Diameter

Quantity

852178

461262

8210G2

Supply

Closed

1/2 inch

1

461263

8262G62

Supply Line Drain

Open

1/4 inch

1

461264

8210G35

Sump Drain

Open

3/4 inch

1

Supply Line

VALVE B

Supply Line Drain Solenoid

(Normally Open)

Sump Overflow

Sump Drain

VALVE C

Sump Drain Solenoid

(Normally Open)

VALVE A

Supply Solenoid

(Normally Closed)

Drain Line

Part numbers subject to change.