Installation - electrical wiring – Greenheck DG / DGX with Direct Spark (464043 IOM) (Pre-2008) User Manual

Page 8

Advertising
background image

8

Step 4 Wire the Optional Convenience Outlet

The convenience outlet requires a separate 115V power supply circuit. The circuit must include short circuit
protection which may need to be supplied by others.

Step 3 Connect the Main Power

Connect the main power lines to the disconnect switch and main grounding lug(s). Torque field connections to
20 in-lbs. See the control center layout in the reference section for main disconnect and grounding lug(s)
locations.

Installation - Electrical Wiring

CAUTION!

If replacement wire is required, it must have a

temperature rating of at least 105°C, except for

energy cut-off or sensor lead wire which must be

rated to 150°C.

CAUTION!

Any wiring deviations may result in personal injury or property damage. Greenheck is not responsible

for any damage to, or failure of the unit caused by incorrect final wiring.

Installation

DANGER!

High voltage electrical input is needed for this

equipment. This work should be performed by a

qualified electrician.

IMPORTANT!

All wiring should be done in accordance with the

latest edition of the National Electrical Code

ANSI/NFPA-70 and any local codes that may

apply. In Canada, wiring should be done in

accordance with the Canadian Electrical Code.

IMPORTANT!

The equipment must be properly grounded.

Any wiring running through the unit in the

airstream must be protected by metal conduit,

metal clad cable or raceways.

Step 1 Determine the Size of the Main

Power Lines

The units nameplate states the voltage and the unit’s
MCA. The main power lines to the unit should be
sized accordingly. The nameplate is located on the
outside of the unit on the control panel side.

Step 2 Provide the Opening(s) for the

Electrical Connections

Electrical openings vary by unit size and arrangement
and are field supplied.

Voltage, Hertz,

and Phase

Unit’s MCA

IMPORTANT!

Before connecting power to the unit, read and understand the following instructions and wiring

diagrams. Complete wiring diagrams are attached to the inside of the control center door(s).

IMPORTANT!

Greenheck’s standard control voltage is 24 VAC.

Control wire resistance should not exceed 0.75 ohms (approximately 285 feet total length for 14 gauge

wire; 455 feet total length for 12 gauge wire). If the resistance exceeds 0.75 ohms an industrial-style,

plug-in relay should be wired in place of the remote switch. The relay must be rated for at least 5

amps and have a 24 VAC coil. Failure to comply with these guidelines may cause motor starters to

chatter or not pull in, resulting in contactor failures and/or motor failures.

Electrical Nameplate

SUP HP

MCA

EXH HP

MOP

VOLTS

HZ

PH