Troubleshooting, Heater does not operate – Greenheck DG / DGX with Direct Spark (464043 IOM) (Pre-2008) User Manual

Page 34

Advertising
background image

34

Troubleshooting

Troubleshooting

24 Vac across

terminals W1 and X?

Heat Switch (S3) Off

(Turn Heat Switch S3 On)
Heat Switch Not Wired

(Wire Heat Switch S3)

24 Vac across

terminals 22 and 21?

Main Transformer Defective

(Replace Transformer)

115 Vac across

terminals 26 and 21?

High/Low Gas Pressure Switch(s) Tripped

(Correct gas pressure and reset)

(Reference Direct Gas Start-Up Step #2)

24 Vac across

terminals 24 and 21?

High Limit (HLC) Tripped

(Reset/Replace High Limit HLC)

(Check on cause of control loss)

Continuity across

terminals 26 and 27?

24 Vac across

terminals 23 and 21?

Inlet Air Senor (TS) Holding

(Adjust TS1 setting -- Reference blower start-up step 6)

Heat Relay (RH) Defective

(Replace Heat Relay RH)

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Airflow Switch (PS) Holding for Proper Airflow

(Correct airflow across burner)

(Reference Direct Gas Start-Up Step #3)

Yes

At this time the heater should attempt to light

Heater Does Not Operate