Start-Up - Direct Gas

Step 6 Set the Minimum Firing Rate

Disconnect and isolate one of the wires running to the modulating valve to send the unit to its minimum firing
rate. Set the minimum firing rate by adjusting the needle valve shown below.

After setting the minimum firing rate, reconnect the wire to the modulating valve.

Minimum

firing rate

adjustment

Remove one wire to

send the unit to the

minimum firing rate.

IMPORTANT!

The proper minimum firing rate setting results in

a small ribbon of continuous flame which covers

the flame rod and runs across the entire burner.

IMPORTANT!

The minimum firing rate setting is critical. If the

settings is too high, the unit may not light, too

low and the flame rod may not detect the flame.

IMPORTANT!

Do not allow the disconnected wire to come in

contact with a potential ground, damage to the

amplifier or transformer could result.

Start-Up

NOTE!

Adjusting the maximum and minimum fire may

require the inlet air sensor to be initially set

higher than desired in order to start the

burner(s). Once high and low fire have been set,

the inlet air sensor should be turned down to the

desired temperature.

NOTE!

Counterclockwise rotation increases the

minimum fire rate setting, clockwise rotation

decreases the setting.

Step 5 Set the Maximum Firing Rate

(...continued)

While monitoring the units temperature rise, set the
maximum firing rate by adjusting the regulator until
the designed temperature rise is achieved. After
setting the maximum firing rate, reconnect the wire to
the amplifier.

IMPORTANT!

Setting the maximum firing rate during mild

weather conditions may cause the high limit to

trip out during extreme conditions requiring

manual resetting.

NOTE!

Clockwise rotation increases the temperature rise, counterclockwise rotation decreases the

temperature rise.

NOTE!

The minimum setting for the maximum firing rate may be higher than required. This is acceptable, the

burner will modulate as needed.

Maximum

firing rate

adjustment

Regulator

Modulating Valve