Location – mhtc reflow hydraulic unit – Nortec MH Series User Manual

Page 17

Advertising
background image

Installation | 14

Location – MHTC Reflow Hydraulic Unit





The MHTC Reflow Hydraulic Unit should be located adjacent to the duct or air handler
containing the MH Duct Module. The Hydraulic Unit is designed to be floor mounted but can be
installed on a stand or raised surface.
 Install the hydraulic unit as close as possible to the MH Duct Unit to minimize length of drain

and spray bar lines.

 Ensure spray bar lines are no longer than 15 ft. vertically (equivalent length per spray bar).

below the top of the duct module.

 Ensure the Hydraulic Unit is installed on a level surface.
 Install providing access for removal of cover and servicing of unit.



















Figure 12: Installation Location / Clearance



Note:.
A P-Trap equal to duct static pressure plus 2 inches must be installed on the drain pan

overflow. Ensure sufficient space is available. Use a stand to raise the drain pan in the

duct if necessary.

Note:

The Duct Unit requires regular maintenance including replacement of media boxes. Ensure

access and sufficient space is provided downstream of the unit to remove and install new

media boxes.

2 in.

(5 cm)

10 in.

(25 cm)

As close as

possible to
spray bars.

5-95%

24 in. (60 cm) Min.

top clearance

Can be placed

as close to duct

as possible

leaving room for

inlet water, drain

and spray bar

connections.

Floor mount to ensure duct module drain pan to hydraulic

unit connection and the drain line can be adequately sloped.

Min. front

clearance

Min. side

clearance

2 in.

(5 cm)

Min. side

clearance

Mount

Hydraulic Unit Level

Drain below drain pan outlet.

Advertising