75 | Troubleshooting

Code

Display

Message

LED

System Detected

Cause

Corrective Action(s)

W20A

Safety Loop

Open

Red

and

Green

Flash

Safety Loop
Open

1 Humidistat open

3 No call for humidity

(normal operation)

2 Air flow blocked

2 Check fan/filter of the

air hancler.

3 Air proving interlock

open

3 If applicable check /

turn on fan.

W21A

Level Sensor

Red

Flash

Defective
controller

1 Level sensor blocked

1 Check that level sensor

can move freely.

E21A

Red

2 Level sensor broken

2 Check if level sensor is

closed when float is

raised. If not replace

sensor.

W22A

Fill Timeout

Red

Flash

Level sensor not
closing when fill
valve on

1 Water supply blocked /

shut off

1 Check shut off valve,

filter, pipes, etc.

2 Water treatment

system regenerating

2 Install relay to interrupt

MH safety loop while

system regenerates.

E22A

Red

3 Low water pressure

3a Check filter
3b Check for leaks in

supply line.

3c Check supply water

pressure

W23A

Drain Timeout

Red

Flash

Float not
opening when
drain valve open

1 Drain valve blocked or

defective.

1 Check / clean / replace

drain valve.

2 Siphon clogged

2 Clean siphon

3 Relay defective

3 Replace control board.

E23A

Red

4 Level sensor stuck or

shorted

4 Clean / replace level

sensor.

5 Pressure equalization

line blocked /

disconnected..

5 Install special siphon.

W25A

μS out of

Range

Red

Flash

Conductivity
sensor reading
out of range

1 Conductivity setting

too low

1 Increase the

conductivity setting in

software.

2 Supply water too

conductive

2 Provide better quality

supply water.

E25A

Red

3 Defective conductivity

sensor

3 Replace conductivity

sensor.

4 Defective transmitter

4 Replace conductivity

transmitter.