General Troubleshooting

The following section provides general guidelines for troubleshooting the MHTC/B humidifier
and auxiliary components. For detailed troubleshooting information refer to the manuals that
were provided with the auxiliary equipment, to Table 6: Troubleshooting Warnings and Faults,
and to Error! Reference source not found. later in this chapter.

Table 5: General Troubleshooting

MH Unit

Problem

Cause

Solution

Residual water in the section
of the duct behind
(downstream) the NORTEC
MH

1 Air velocity through the media boxes is
too high.
Reference
Units without mist eliminator max. (750
fpm) 3.8 m/s.
Units with a mist eliminator max. 1082
fpm (5.5 m/s).

1 Install mist eliminator or

reduce air velocity in the

duct.

2 Water drain is leaking.

2 Check/seal water drain.

Humidity/cooling demand
present however the NORTEC
MH does not humidify.

1 Shut-off valve in the water supply line
closed.

1 Open shut-off valve.

2 Reflow models: circulation pump
defective.

2 Replace circulation pump.

Maximum
humidification/cooling
Capacity is not reached.

1 System incorrectly dimensioned

(insufficient capacity).

1 Contact your NORTEC

supplier.

2 Unit improperly configured.

2 Check unit configuration.

3 Safety opens intermittently.

3 Defective sensors.

4 Inlet temperature low.

4 Increase the temperature of

the air passing through the

MH.

5 Insufficient water supply capacity

5 Check water supply, increase

water pressure.

6 Models with MH control unit: output

limitation active.

6 Deactivate output limitation

(see separate operating

instructions for MH control

unit).

Pump running (>5 min.)
however no water out of
staging valves.

1 Blockage in the bypass tube in the

manifold block preventing the pump
from purging air from the system.

1 Check for dirt or debris in the

bypass tube in the manifold

block. Use a small wire or

pipe cleaner to clean the

bypass channel in the

manifold block (stage 2 valve

will need to be removed).