Installation | 22

Plumbing

General

 All water supply and drain line connections must be installed in accordance with local

plumbing codes.

 Install water shut off valve and union before humidifier to facilitate servicing.
 Insure drain line and overflow line are min 1.25 in. (32 mm) ID. to provide draining.
 High hardness supply water will require increased maintenance and more frequent

replacement of evaporative media.

 Unit damage caused by water quality outside of the specified ranges is not covered under

warranty.

Note:

 Supply untreated potable water, reverse osmosis water, fully demineralised water or

partly softened water. Do not treat water with corrosion inhibitors, disinfectants or other

chemicals.

 If fully demineralised water is used then use plastic or stainless steel components for

all plumbing connections.

 Flush water lines thoroughly before connecting to the hydraulic unit.