39 | Start Up


6 The green On LED on the front of the humidifier will be on. On the MHTC the display will

indicate either Demand or Actual Humidity and Setpoint depending on control configuration.










MHTC Status Screens

In addition to the main status screen the MHTC includes several status screens which provide
additional information about the humidifier. The additional screens can be reached by pressing
the buttons corresponding to the left and right arrow key on the LCD display.

Main Status Screen

This screen reports the current request for humidity or actual
humidity and setpoint depending on control configuration. It
also displays the date and time.
Pressing a button corresponding to an arrow displays screens
providing additional information on the status of the
humidifier.
Pressing the Menu button displays a Main Menu screen which
includes an Info selection to display

Settings Information Screen

Software = the installed software version.
Hum. Control = the type of control configuration (External,
24VonOff,Int. (P), or Int. (PI))
Control sign = the configured control signal range.
Modbus Addr = the configured Modbus Address.





Caution:
 Improper control configuration can result in over humidifying which can result in

damage to property.

 See Advanced Control Configuration if the controls displayed in the Settings

Information Screen do not match those connected to the MHTC.

Note: During Operation
 The pump will stop for 4 seconds every 30 minutes to clear trapped air and

staging valve(s) will close every 30 minutes for 2 seconds to prevent them from

scaling open.

 Cleaning / Draining / Box Drying will occur based on configuration.