Options and accessories – Nortec MH Series User Manual

Page 37

Advertising
background image

Installation | 34

Options and Accessories

Mist Eliminator

Mist eliminators are available for all MH models. At higher velocities there is a chance that
water droplets can be picked up by the air flowing through the media and carried into the air
duct. The mist eliminator acts a barrier to the droplets and prevents them from entering the
duct. Mist eliminators should be used in applications where duct velocity is higher than 750 fpm
(3.8 m/s).
To install a mist eliminator first follow the assembly instructions that are provided with it and
then install it in the MH duct module as shown in Step 8 – Install Mist Eliminator on page 19.

Conductivity Sensor (MHTC Reflow Only)

A conductivity sensor is available for the MHTC Reflow which provides the ability to better
control the amount of minerals that are suspended in the recirculating water. Normally the
MHTC controller will flush water from the reservoir based on operating time. With the
conductivity sensor installed the controller will flush the water only when the conductivity rises
above a user configurable limit. This results in less waste water and longer media life.
The conductivity sensor can be installed at the factory or ordered as a field installed accessory.
To install the conductivity sensor follow the instructions that come with it. See Clean Trg. 2 =
μSSensor on page 54 for information on configuring the conductivity function of the MHTC
controller.

Note:
For installation of options and accessories follow the instructions that are provided with

them.

Advertising