MHTC Warnings and Faults

The self-diagnostic system built into the MHTC is continually monitoring its operation.

Warnings

 When problem symptoms are detected, the MHTC will attempt to take self-corrective actions

to try to correct the problem. The display will show a “W” followed by the warning code for
information purposes and the MHTC will continue to operate.

 If the condition which generated the warning is eliminated the warning is cleared from the

display.

Faults

 If the MHTC is not able to self correct a problem symptom it will if necessary respond by

shutting itself down.

 When this occurs the MHTC illuminates the red “Fault” LED, Displays an “F” followed by the

fault code on the display, drains the reservoir, and activates the “Error” relay of the remote
relay board.

Clearing a Fault

 Check the fault message that the MHTC is displaying and take any necessary actions to

correct the cause(s) as outlined in Table 6, Troubleshooting Warnings and Faults.

 Power cycle the MHTC with the On/Off switch waiting 3 seconds between turning it off and

on.

Table 6: Troubleshooting Warnings and Faults

Code

Display

Message

LED

System Detected

Cause

Corrective Action(s)

W1

MH Card
Missing

Red
Flash

No MH Card

1 No MH Card installed

on the control board

1 Install MH Card or start

test run.

E1 Red

E2

MH Card Empty Red

No data on MH
Card

1 No data stored on the

MH Card

1 Install new MH Card

E3

MH Card Invalid Red

Invalid MH Card

1 Invalid data stored on

the MH Card

1 Install new MH Card.

E4

MH Card
Incompat

Red

Incompatible
MH Card

1 The MH card is not

compatible with the

hardware or the basic

settings of the control

board.

1a Install new MH Card
1b Modify basic settings.

E5

Module B
Missing

Red

No response
from Module B

1 Flat ribbon cable

broken or

disconnected

1a Plug in flat ribbon

cable.

1b Replace ribbon cable.

1 120V supply cable

disconnected

1 Plug in 120V supply

cable to module B

Advertising