53 | Operation

Cleaning Mode (MHTC Reflow Only)
Sets whether the MHTC Reflow will
rinse media and flush the tank or
simply flush the tank during cleaning
cycles. Drain = only flush tank, Wash
= rinse media and flush tank.

Cleaning Triggers

Cleaning is used to remove minerals left behind by evaporated water. Cleaning triggers are used
by the MHTC to determine when cleaning cycles will take place. For the MHTC Reflow the
cleaning cycle performed depends on the setting of the Clean Mode parameter. For the MHTC

flow the cleaning always consists of activating the staging valves and washing the media.

Cleaning Trg. 1

Can be turned off for the MHTC Flow, the option to turn the trigger Off does not appear for the
MHTC Reflow. To set the type of trigger to use highlight Clean Trg. 1 and press Set.

Clean Trg. 1 = Periodic
The cleaning cycle is triggered after a
fixed number of operating hours.
Periodic Int = hours between
cleaning cycles.


Clean Trg. 1 = Timer
The cleaning cycle is triggered at up
to four specific times of day. Set
each time of day by highlighting it
and pressing Set. Turn the timer On
and adjust the time in the screen
that is displayed.


Cleaning Trg. 2

Is only displayed for the MHTC Reflow. The trigger can be turned off in which case only Clean
Trg. 1 will be used to initiate MHTC Reflow cleaning cycles.

Clean Trg. 2 = Cycle
The cleaning cycle is triggered after a
fixed number of fill cycles. To set the
number of fill cycles between
cleaning highlight Fill Cycle and press
Set. On the screen displayed use
Up/Down arrows to change the
value. Press Set to confirm the
setting.



Clean Trg. 1
Clean Trg. 1

: Periodic

Time 1

: On 23:00

Time 2

: Of - -:- -

Time 3

: Of - -:- -

Time 4

: Of - -:- -

Esc

Set

Clean Trg. 1

: Timer

(MHTC Reflow Only)

(MHTC Reflow Only)