Digital humidistat – Nortec MH Series User Manual

Page 76

Advertising
background image

73 | Troubleshooting

Digital Humidistat

Symptom

Cause

Corrective Action(s)

Humidistat Reading incorrectly

1 Sensor out of calibration

1 Check reading against known

reliable instrument. If out of

calibration it can be field calibrated
±10%. Press buttons together

until calH appears on the display.
Press to display the current
calibration trim. Adjust using 

buttons. Press  button when done.

2 Improper sensor location

2 Check that the humidistat is

positioned in a location

representative of room humidity.

3 Exposed to draft or heat source

3 Check that heat/cold fluctuations,

drafts, sunlight, doors, or vents are

affecting the reading.

4 No vapour barrier

4 Insure drafts cannot affect reading

by ensuing vapour barrier is in place

and working.

Advertising