Drive, 3 electrical installation, Figure 4 drive standard connection diagram – Yaskawa A1000 6-Phase/12-Pulse Input User Manual

Page 16

Advertising
background image

+

+

-

+

+

+

-

+

+

S

1

S

2

S

3

S

4

S

5

S

6

S

7

MP

DM

DM

RP

A

1

A

2

A

3

0 V

AC

R
R
S
S-

IG

H

1

H

2

HC

Drive

2 k

S

8

SC

0 V

0 V

AC

FM

AM
AC

E (G)

S

1

S

2

<11>

<6>

<12>

<13>

<8>

<10>

<6>

<4>

<3>

+

24 V

+

V

MA

M

1

M

2

MB
MC

Forward Run / Stop

Reverse Run / Stop

External fault

Fault reset

Multi-speed step 1

Multi-speed step 2

External Baseblock

Jog speed

Multi-function

digtial inputs

(default setting)

Sink / Source mode

selection wire link

(default: Sink)

CN5-C

CN5-B

CN5-A

Option board

Pulse Train Input
(max 32 kHz)

Shield ground
terminal

Multi-function

analog/pulse

train inputs

Power supply +10.5 Vdc, max. 20 mA

Analog Input 1 (Frequency Reference Bias)

-10 to +10 Vdc (20 k )

Analog Input 2 (Frequency Reference Bias)

-10 to +10 Vdc (20 k )

0 or 4 to 20 mA (250 )

Analog Input 3 / PTC Input (Aux. frequency

reference)

-10 to +10 Vdc (20 k )

-

V

Power supply, -10.5 Vdc, max. 20 mA

Safety

switch

MEMOBUS/Modbus comm.

RS-422/RS-485

max. 115.2 kBps

Safe Disable inputs

Wire

jumper

Open

Safety relay /

controller

Termination resistor

(120 , 1/2 W)

DIP

Switch S2

Fault relay output

250 Vac, max. 1 A

30 Vdc, max 1 A

(min. 5 Vdc, 10 mA)

Multi-function relay output (During Run)

250 Vac, max. 1 A

30 Vdc, max 1 A

(min. 5 Vdc, 10 mA)

Multi-function pulse train output

(Output frequency)

0 to 32 kHz (2.2 k )

Multi-function analog output 1
(Output frequency)

-10 to +10 Vdc (2mA)
or 4 to 20 mA

EDM (Safety Electronic Device Monitor)

Control Circuit

shielded line

twisted-pair shielded line

main circuit terminal

control circuit terminal

M

3

M

4

Multi-function relay output (Zero Speed)

250 Vac, max. 1 A

30 Vdc, max 1 A

(min. 5 Vdc, 10 mA)

M

5

M

6

Multi-function relay output (Speed Agree 1)

250 Vac, max. 1 A

30 Vdc, max 1 A

(min. 5 Vdc, 10 mA)

SP

SN

<9>

AM

FM

V

I

V

I

DIP Switch S1

A2 Volt/Curr. Sel

DIP Switch S4

A3 Analog/PTC

Input Sel

PTC

AI

Off

On

DIP Switch S2

Term. Res. On/Off

Jumper S3
H1, H2
Sink/Source Sel.

Jumper S5

AM/FM Volt./Curr.

Selection

Terminal board

jumpers and switches

FM

+

AM

<5>

<14>

<13>

Multi-function analog output 2
(Output current)

-10 to +10 Vdc (2mA)
or 4 to 20 mA

<15>

<6>

A+
A-

B-

Z-

B+

Z+

a+
a-
b+
b-
z+
z-

FE

IP
IG

TB1

SD

TB2

B track monitor

A track monitor

M

U/T

1

V/T

2

W/T

U

FU
FV
FW

V

W

3

Ground

Cooling fan

PG

M

PG- X3

connectors

(option)

Slide Switch S6

DM+, DM-

N.C./N.O. Selection

N.C.

N.O.

<7>

Terminals B1, B2, -, and +3, B1
are for power option connections.
Never connect power supply lines
to these terminals

B1 B2

Fuse

Main Circuit

Three-Phase
Power Supply
380 to 480 V
50/60 Hz

Wiring sequence should shut off
power to the drive when a fault
output is triggered.

BCP

R/L1
S/L2
T/L3
R1/L11
S1/L21
T1/L31

R
S
T

Main

Switch

Models 4T0058 and 4T0072
Dynamic braking resistor
(option)

<1> <2>

U1
V1
W1

W2

V2

U2

-

+3

Models 4T0088 to 4T0675
CDBR dynamic braking unit
(option)

<1> <2>

<16>

<17>

Figure 4 Drive Standard Connection Diagram

3 Electrical Installation

16

YASKAWA TOEP YAIA1U 02A YASKAWA AC Drive – A1000 6-Phase/12-Pulse Input Installation Manual